Contactor LC1E160M5

Model: 004.005.183
Contactor LC1E160M5
Manufacturer: Schneider Electric
Barcode: 3606480323751
The E-line contactors LC1E160M5 1NO+1NC 160A 380V AC3 220V/50Hz offer proven performance for resistive loads or large motor starting applications such as fans, crushers, pumps, compressors and overhead cranes. They offer high reliability with long mechanical and electrical life and the most complete line of accessories in the industry.
Price by call

Main

rangeEasyPact
product nameEasyPact TVS
product or component typeContactor
device short nameLC1E
contactor applicationResistive load
Motor control
utilisation categoryAC-1
AC-3
poles description3P
power pole contact composition3 NO
[Ue] rated operational voltagePower circuit: ≤ 690 V AC 50/60 Hz
[Ie] rated operational current160 A (at < 55 °C) at ≤ 440 V AC AC-3 for power circuit
200 A (at < 55 °C) at ≤ 440 V AC AC-1 for power circuit
motor power kW45 kW at 220...230 V AC 50/60 Hz
75 kW at 380...400 V
80 kW at 415 V
80 kW at 440 V
90 kW at 500 V
100 kW at 660...690 V
control circuit typeAC at 50 Hz
[Uc] control circuit voltage220 V AC 50 Hz
height158 mm
width120 mm
depth132 mm
net weight2.3 kg

Complementary

auxiliary contact composition1 NO + 1 NC
[Uimp] rated impulse withstand voltage8 kV coil not connected to the power circuit conforming to IEC 60947
[Ui] rated insulation voltage690 V conforming to IEC 60947-4-1
overvoltage categoryIII
Irms rated making capacity1600 A at 440 V AC for power circuit conforming to IEC 60947-4-1
rated breaking capacity1280 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current1400 A 40 °C - 10 s for power circuit
associated fuse rating10 A gG at ≤ 690 V coordination type 1 for control circuit conforming to IEC 60947-5-1
315 A gG at ≤ 690 V coordination type 1 for power circuit
average impedance0.6 mOhm - Ith 200 A 50 Hz for power circuit
power dissipation per pole24 W AC-1
15 W AC-3
control circuit voltage limitsOperational: 0.85...1.1 Uc at 50 Hz (at < 55 °C)
Drop-out: 0.35...0.55 Uc at 50 Hz (at < 55 °C)
operating time20...50 ms on closing
6...20 ms on opening
mechanical durability400000 cycles
maximum operating rate1200 cyc/h 55 °C
inrush power in VA300 VA 50 Hz cos phi 0.9 (at 20 °C)
300 VA 60 Hz cos phi 0.9 (at 20 °C)
hold-in power consumption in VA22 VA 50 Hz cos phi 0.9 (at 20 °C)
22 VA 60 Hz cos phi 0.9 (at 20 °C)
heat dissipation3…8 W for control circuit
minimum switching current5 mA for control circuit
minimum switching voltage17 V for control circuit
non-overlap time1.5 ms on energisation guaranteed between NC and NO contact
1.5 ms on de-energisation guaranteed between NC and NO contact
insulation resistance> 10 MOhm for control circuit
electrical durability800000 cycles AC-3
250000 cycles AC-1
mounting supportPlate
DIN rail
connections - terminalsControl circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end
Power circuit: screw clamp terminals 1 10…120 mm² - cable stiffness: flexible with cable end
Power circuit: screw clamp terminals 1 10…120 mm² - cable stiffness: solid without cable end
Control circuit: screw clamp terminals 1 1…2.5 mm² - cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 1 1…2.5 mm² - cable stiffness: flexible with cable end
Control circuit: screw clamp terminals 1 1…2.5 mm² - cable stiffness: solid without cable end
Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: solid without cable end
Power circuit: screw clamp terminals 2 10…120 mm² - cable stiffness: flexible with cable end
Power circuit: screw clamp terminals 2 10…120 mm² - cable stiffness: solid without cable end
Recommended tightening torquePower circuit: 12 N.m
Control circuit: 1.2 N.m
Max tightening torquePower circuit: 13.5 N.m
Control circuit: 1.4 N.m

Environment

standardsIEC 60947-4-1
IEC 60947-1
IEC 60947-5-1
product certificationsEAC
IP degree of protectionIP2x conforming to IEC 60529
protective treatmentTH (pollution degree 3) conforming to IEC 60068
pollution degree3
ambient air temperature for operation-5…55 °C
ambient air temperature for storage-60…80 °C
permissible ambient air temperature around the device-20…70 °C at Uc
operating altitude3000 m without derating
fire resistance850 °C conforming to IEC 60695-2-1
mechanical robustnessVibrations contactor open: 1.5 Gn, 5...300 Hz
Vibrations contactor closed: 3 Gn, 5...300 Hz
Shocks contactor open: 6 Gn for 11 ms
Shocks contactor closed: 7 Gn for 11 ms

Dimensions and internal circuit

dimensions of LC1E160M5 circuit of LC1-E160M5

Auxiliaries and accessories for LC1E160M5

Similar or replacement products LC1E160M5

Вопрос-ответ
Product categories