Contactor LC1BR33M22

Model: 004.013.015
Contactor LC1BR33M22
Manufacturer: Schneider Electric
Barcode: 3389110103106
The B-line contactors offer proven performance for resistive loads or large motor starting applications such as fans, crushers, pumps, compressors and overhead cranes. They offer high reliability with long mechanical and electrical life and the most complete line of accessories in the industry.
Price by call

Main

rangeTeSys
product nameTeSys B
product or component typeContactor
device short nameLC1BR
contactor applicationMotor-heating-lighting
utilisation categoryAC-3
AC-1
control circuit typeAC
coil typeStandard
poles description3P
pole contact composition3 NO
[Ie] rated operational current2750 A (at < 40 °C) AC AC-1 for power circuit
1800 A (at < 55 °C) AC AC-3 for power circuit
motor power kW500 kW at 220...230 V AC 50/60 Hz (AC-3)
750 kW at 1000 V AC 50/60 Hz (AC-3)
900 kW at 380...400 V AC 50/60 Hz (AC-3)
900 kW at 415 V AC 50/60 Hz (AC-3)
900 kW at 440 V AC 50/60 Hz (AC-3)
900 kW at 500 V AC 50/60 Hz (AC-3)
900 kW at 660...690 V AC 50/60 Hz (AC-3)
250 kW at 400 V AC 50/60 Hz (AC-4)
auxiliary contact composition2 NO + 2 NC
[Uc] control circuit voltage220 V AC 50...400 Hz

Complementary

control circuit voltage limitsDrop-out: 0.4...0.5 Uc at 50...400 Hz
Operational: 0.85...1.1 Ucw at 50...400 Hz
[Ui] rated insulation voltage1000 V - for power circuit conforming to IEC 60158-1
1000 V - for power circuit conforming to IEC 60947-4
1500 V - for power circuit conforming to VDE 0110 group C
mounting modeFixed
mounting supportNotched mounting rails
Bar support bracket
connections - terminalsPower circuit: bars 4 x - busbar cross section: 100 x 5 mm
tightening torquePower circuit: 35 N.m - on bars
[Ue] rated operational voltagePower circuit: ≤ 1000 V AC 50/60 Hz
[Ith] conventional free air thermal current2750 A (at 40 °C) for power circuit
Irms rated making capacity18000 A at 1000 V AC for power circuit conforming to IEC 60158-1
18000 A at 1000 V AC for power circuit conforming to IEC 60947-4
rated breaking capacity11000 A at 660...690 V for power circuit conforming to IEC 60158-1
11000 A at 660...690 V for power circuit conforming to IEC 60947-4
15000 A at 500 V for power circuit conforming to IEC 60158-1
15000 A at 500 V for power circuit conforming to IEC 60947-4
18000 A at 440 V for power circuit conforming to IEC 60158-1
18000 A at 440 V for power circuit conforming to IEC 60947-4
6000 A at 1000 V for power circuit conforming to IEC 60158-1
6000 A at 1000 V for power circuit conforming to IEC 60947-4
associated fuse rating2000 A aM at ≤ 440 V for power circuit
2400 A gI at ≤ 440 V for power circuit
average impedance0.09 mOhm - Ith 2750 A 50 Hz for power circuit
power dissipation per pole360 W AC-3 - Ith 2750 A
680 W AC-1 - Ith 2750 A
inrush power in VA1300 VA
hold-in power consumption in VA31 VA 50/60 Hz
operating time100...150 ms closing
50...100 ms opening
mechanical durability1200000 cycles
maximum operating rate120 cyc/h 55 °C
height495 mm
width915 mm
depth475 mm
net weight129 kg

Environment

standardsBS 5424
IEC 60158-1
IEC 60947-4
VDE 0660
NF C 63-110
product certificationsBV
CSA
RINA
protective treatmentTC
TH
ambient air temperature for operation-5…55 °C
ambient air temperature for storage-60…80 °C
operating altitude3000 m without derating

Auxiliaries and accessories for LC1BR33M22

Similar or replacement products LC1BR33M22