TeSys D series contactor LC1D25BD

Model: 004.001.109
Contactor LC1D25BD
Manufacturer: Schneider Electric
Barcode: 3389110355994
Contactor LC1D25BD is mainly used in AC circuits 50Hz (60Hz), rated voltage up to 660V, current up to 25A for controlling motors operation in AC-3 and AC-1.
Coil voltage 24VDC.
Operating temperature -5°C…+60°C.
Price by call

Main

rangeTeSys
product nameTeSys D
product or component typeContactor
device short nameLC1D
contactor applicationMotor control
Resistive load
utilisation categoryAC-4
AC-3
AC-1
poles description3P
power pole contact composition3 NO
[Ue] rated operational voltagePower circuit: ≤ 690 V AC 25...400 Hz
Power circuit: ≤ 300 V DC
[Ie] rated operational current25 A (at < 60 °C) at ≤ 440 V AC AC-3 for power circuit
40 A (at < 60 °C) at ≤ 440 V AC AC-1 for power circuit
motor power kW5.5 kW at 220...230 V AC 50/60 Hz (AC-3)
11 kW at 380...400 V AC 50/60 Hz (AC-3)
11 kW at 415...440 V AC 50/60 Hz (AC-3)
15 kW at 500 V AC 50/60 Hz (AC-3)
15 kW at 660...690 V AC 50/60 Hz (AC-3)
5.5 kW at 400 V AC 50/60 Hz (AC-4)
motor power HP (UL / CSA)3 hp at 230/240 V AC 50/60 Hz for 1 phase motors
2 hp at 115 V AC 50/60 Hz for 1 phase motors
7.5 hp at 230/240 V AC 50/60 Hz for 3 phases motors
15 hp at 460/480 V AC 50/60 Hz for 3 phases motors
20 hp at 575/600 V AC 50/60 Hz for 3 phases motors
7.5 hp at 200/208 V AC 50/60 Hz for 3 phases motors
control circuit typeDC standard
[Uc] control circuit voltage24 V DC
auxiliary contact composition1 NO + 1 NC
[Uimp] rated impulse withstand voltage6 kV conforming to IEC 60947
overvoltage categoryIII
[Ith] conventional free air thermal current10 A (at 60 °C) for signalling circuit
40 A (at 60 °C) for power circuit
Irms rated making capacity140 A AC for signalling circuit conforming to IEC 60947-5-1
250 A DC for signalling circuit conforming to IEC 60947-5-1
450 A at 440 V for power circuit conforming to IEC 60947
rated breaking capacity450 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current240 A 40 °C - 10 s for power circuit
380 A 40 °C - 1 s for power circuit
50 A 40 °C - 10 min for power circuit
120 A 40 °C - 1 min for power circuit
100 A - 1 s for signalling circuit
120 A - 500 ms for signalling circuit
140 A - 100 ms for signalling circuit
associated fuse rating10 A gG for signalling circuit conforming to IEC 60947-5-1
63 A gG at ≤ 690 V coordination type 1 for power circuit
40 A gG at ≤ 690 V coordination type 2 for power circuit
average impedance2 mOhm - Ith 40 A 50 Hz for power circuit
[Ui] rated insulation voltagePower circuit: 690 V conforming to IEC 60947-4-1
Power circuit: 600 V CSA certified
Power circuit: 600 V UL certified
Signalling circuit: 690 V conforming to IEC 60947-1
Signalling circuit: 600 V CSA certified
Signalling circuit: 600 V UL certified
electrical durability1.65 Mcycles 25 A AC-3 at Ue ≤ 440 V
1.4 Mcycles 40 A AC-1 at Ue ≤ 440 V
power dissipation per pole3.2 W AC-1
1.25 W AC-3
Front coverWith
mounting supportPlate
Rail
standardsCSA C22.2 No 14
EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 508
product certificationsLROS (Lloyds register of shipping)
BV
GL
CCC
RINA
GOST
CSA
DNV
UL
connections - terminalsControl circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end
Power circuit: screw clamp terminals 1 cable(s) 2.5…10 mm²flexible without cable end
Power circuit: screw clamp terminals 2 cable(s) 2.5…10 mm²flexible without cable end
Power circuit: screw clamp terminals 1 cable(s) 1…10 mm²flexible with cable end
Power circuit: screw clamp terminals 2 cable(s) 1.5…6 mm²flexible with cable end
Power circuit: screw clamp terminals 1 cable(s) 1.5…10 mm²solid without cable end
Power circuit: screw clamp terminals 2 cable(s) 2.5…10 mm²solid without cable end
tightening torqueControl circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
Power circuit: 2.5 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
Power circuit: 2.5 N.m - on screw clamp terminals - with screwdriver Philips No 2
operating time53.55...72.45 ms closing
16...24 ms opening
safety reliability levelB10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
mechanical durability30 Mcycles
maximum operating rate3600 cyc/h 60 °C

Complementary

coil technologyBuilt-in bidirectional peak limiting diode suppressor
control circuit voltage limits0.1...0.25 Uc (-40…70 °C):drop-out DC
0.7...1.25 Uc (-40…60 °C):operational DC
1...1.25 Uc (60…70 °C):operational DC
time constant28 ms
inrush power in W5.4 W (at 20 °C)
hold-in power consumption in W5.4 W at 20 °C
auxiliary contacts typetype mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
type mirror contact 1 NC conforming to IEC 60947-4-1
signalling circuit frequency25...400 Hz
minimum switching current5 mA for signalling circuit
minimum switching voltage17 V for signalling circuit
non-overlap time1.5 ms on de-energisation between NC and NO contact
1.5 ms on energisation between NC and NO contact
insulation resistance> 10 MOhm for signalling circuit

Environment

IP degree of protectionIP20 front face conforming to IEC 60529
protective treatmentTH conforming to IEC 60068-2-30
pollution degree3
ambient air temperature for operation-40…60 °C
60…70 °C with derating
ambient air temperature for storage-60…80 °C
operating altitude0...3000 m
fire resistance850 °C conforming to IEC 60695-2-1
flame retardanceV1 conforming to UL 94
mechanical robustnessVibrations contactor open: 2 Gn, 5...300 Hz
Vibrations contactor closed: 4 Gn, 5...300 Hz
Shocks contactor closed: 15 Gn for 11 ms
Shocks contactor open: 8 Gn for 11 ms
height85 mm
width45 mm
depth101 mm
net weight0.53 kg

Dimensions and internal circuit

Dimension LC1D25BD
Contactor LC1D25BD wiring diagram

3-pole contactors LC1D with coil 230Vac 50/60Hz

Model Rated operational voltage AC-3 (Ue ≤ 400V), A Standard power ratings of 3-phase motors 50-60 Hz in category AC-3 (t≤60°C), kW
220V/230V 380V/400V 415V 440V 500V 660V/690V 1000V
LC1D09BD 9 2,2 4 4 4 5,5 5,5 -
LC1D12BD 12 3 5,5 5,5 5,5 7,5 7,5 -
LC1D18BD 18 4 7,5 9 9 10 10 -
LC1D25BD 25 5,5 11 11 11 15 15 -
LC1D32BD 32 7,5 15 15 15 18,5 18,5 -
LC1D38BD 38 9 18,5 18,5 18,5 18,5 18,5 -
LC1D40ABD 40 11 18,5 22 22 22 30 22
LC1D50ABD 50 15 22 25 30 30 33 30
LC1D65ABD 65 18,5 30 37 37 37 37 37
LC1D80BD 80 22 37 45 45 55 45 45
LC1D95BD 95 25 45 45 45 55 45 45
LC1D115BD 115 30 55 59 59 75 80 75
LC1D150BD 150 40 75 80 80 90 100 90

Standard control circuit voltages on 42Vac 50/60Hz

a.c. supply
Voltage, V 24 42 48 110 115 220 230 240 380 400 415 440 500
LC1-D09..D150 (D115 and D150 coils with integral suppression device fitted as standard)
50/60Hz B7 D7 E7 F7 FE7 M7 P7 U7 Q7 V7 N7 R7 -
LC1-D40...D115
50Hz B5 D5 E5 F5 FE5 M5 P5 U5 Q5 V5 N5 R5 S5
60Hz B6 - E6 F6 - M6 - U6 Q6 - - R6 -
d.c. supply
Voltage, V 12 24 36 48 60 72 110 125 220 250 440
LC1-D09...D38 (coils with integral suppression device fitted as standard)
U 0,7…1,25 Uc JD BD CD ED ND SD FD GD MD UD RD
LC1-D40...D95
U 0,85…1,1 Uc JD BD CD ED ND SD FD GD MD UD RD
U 0,75…1,2 Uc JW BW CW EW - SW FW - MW - -
LC1-D115 and D150 (coils with integral suppression device fitted as standard)
U 0,75…1,2 Uc - BD - ED ND SD FD GD MD UD RD
Low consumption
Volatage DC 5 12 20 24 48 110 220 250
LC1-D09..D38 (coils with integral suppression device fitted as standard)
U 0,7...1,25 Uc AL JL ZL BL EL FL ML UL

Auxiliaries and accessories for LC1D25BD

Similar or replacement products LC1D25BD