Contactor LC1F265BD

Model: 004.007.096
Contactor LC1F265BD
Manufacturer: Schneider Electric
Barcode: 3389118095403
The F-line contactors offer proven performance for resistive loads or large motor starting applications such as fans, crushers, pumps, compressors and overhead cranes. They offer high reliability with long mechanical and electrical life and the most complete line of accessories in the industry.
Price by call

Main

Main
rangeTeSys
product nameTeSys F
product or component typeContactor
device short nameLC1F
contactor applicationResistive load
Motor control
utilisation categoryAC-3
AC-1
AC-4
poles description3P
power pole contact composition3 NO
[Ue] rated operational voltage≤ 1000 V AC 50/60 Hz
≤ 460 V DC
[Ie] rated operational current350 A (at < 40 °C) at ≤ 440 V AC AC-1
265 A (at < 55 °C) at ≤ 440 V AC AC-3
motor power kW132 kW at 380...400 V AC 50/60 Hz (AC-3)
140 kW at 415 V AC 50/60 Hz (AC-3)
140 kW at 440 V AC 50/60 Hz (AC-3)
160 kW at 500 V AC 50/60 Hz (AC-3)
160 kW at 660...690 V AC 50/60 Hz (AC-3)
147 kW at 1000 V AC 50/60 Hz (AC-3)
75 kW at 220...230 V AC 50/60 Hz (AC-3)
51 kW at 400 V AC 50/60 Hz (AC-4)
[Uc] control circuit voltage24 V DC
coil typeStandard
Complementary
[Uimp] rated impulse withstand voltage8 kV
overvoltage categoryIII
[Ith] conventional free air thermal current350 A (at 40 °C)
rated breaking capacity2120 A conforming to IEC 60947-4-1
[Icw] rated short-time withstand current2200 A 40 °C - 10 s
1230 A 40 °C - 30 s
950 A 40 °C - 1 min
620 A 40 °C - 3 min
480 A 40 °C - 10 min
associated fuse rating315 A aM at ≤ 440 V
400 A gG at ≤ 440 V
average impedance0.3 mOhm - Ith 350 A 50 Hz
[Ui] rated insulation voltage1000 V conforming to IEC 60947-4-1
1500 V conforming to VDE 0110 group C
power dissipation per pole37 W AC-1
21 W AC-3
mounting supportPlate
standardsJIS C8201-4-1
IEC 60947-1
EN 60947-1
IEC 60947-4-1
EN 60947-4-1
product certificationsLROS (Lloyds register of shipping)
ABS
RINA
BV
CSA
UL
RMRoS
DNV
CB
connections - terminalsControl circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end
Power circuit: bar 2 cable(s) - busbar cross section: 32 x 4 mm
Power circuit: lugs-ring terminals 1 cable(s) 240 mm²
Power circuit: connector 1 cable(s) 240 mm²
Power circuit: bolted connection
tightening torqueControl circuit: 1.2 N.m
Power circuit: 35 N.m
control circuit voltage limitsOperational: 0.85...1.1 Uc (at 55 °C)
Drop-out: 0.15...0.2 Uc (at 55 °C)
inrush power in W750 W (at 20 °C)
hold-in power consumption in W5 W at 20 °C
heat dissipation5 W
operating time40...50 ms closing
40...65 ms opening
mechanical durability10 Mcycles
maximum operating rate2400 cyc/h 55 °C
compatibility codeLC1F
motor power range55…100 kW at 200…240 V 3 phases
110…220 kW at 480…500 V 3 phases
110…220 kW at 380…440 V 3 phases
motor starter typeDirect on-line contactor
contactor coil voltage24 V DC standard
Environment
IP degree of protectionIP20 front face with shrouds conforming to IEC 60529
IP20 front face with shrouds conforming to VDE 0106
protective treatmentTH
ambient air temperature for operation-5…55 °C
ambient air temperature for storage-60…80 °C
permissible ambient air temperature around the device-40…70 °C
height203 mm
width201.5 mm
depth213 mm
net weight7.44 kg

Dimensions

Dimensions of contactor LC1F265BD

Auxiliaries and accessories for LC1F265BD