Contactor LC1F800MW 3P 800 A

Model: 004.007.026
Contactor LC1F800MW 3P 800 A
Manufacturer: Schneider Electric
Barcode: 3389110790610
The F-line contactors offer proven performance for resistive loads or large motor starting applications such as fans, crushers, pumps, compressors and overhead cranes. They offer high reliability with long mechanical and electrical life and the most complete line of accessories in the industry.
Coil LX4F8MW - 220Vdc
Price by call
Main
rangeTeSys
product nameTeSys F
product or component typeContactor
device short nameLC1F
contactor applicationMotor control
Resistive load
utilisation categoryAC-4
AC-1
AC-3
poles description3P
power pole contact composition3 NO
[Ue] rated operational voltage≤ 1000 V AC 50/60 Hz
≤ 460 V DC
[Ie] rated operational current1000 A (at < 40 °C) at ≤ 440 V AC AC-1
800 A (at < 55 °C) at ≤ 440 V AC AC-3
motor power kW450 kW at 1000 V AC 50/60 Hz (AC-3)
450 kW at 500 V AC 50/60 Hz (AC-3)
475 kW at 660...690 V AC 50/60 Hz (AC-3)
110 kW at 400 V AC 50/60 Hz (AC-4)
450 kW at 380...400 V AC 50/60 Hz (AC-3)
450 kW at 415 V AC 50/60 Hz (AC-3)
450 kW at 440 V AC 50/60 Hz (AC-3)
250 kW at 220...230 V AC 50/60 Hz (AC-3)
[Uc] control circuit voltage220...230 V DC
220...240 V AC 40...400 Hz
coil typeStandard
Complementary
[Uimp] rated impulse withstand voltage8 kV
overvoltage categoryIII
[Ith] conventional free air thermal current1000 A (at 40 °C)
rated breaking capacity6400 A conforming to IEC 60947-4-1
[Icw] rated short-time withstand current5500 A 40 °C - 10 s
4600 A 40 °C - 30 s
3600 A 40 °C - 1 min
2600 A 40 °C - 3 min
1700 A 40 °C - 10 min
associated fuse rating1000 A gG at ≤ 440 V
800 A aM at ≤ 440 V
average impedance0.12 mOhm - Ith 1000 A 50 Hz
[Ui] rated insulation voltage1000 V conforming to IEC 60947-4-1
1500 V conforming to VDE 0110 group C
power dissipation per pole120 W AC-1
77 W AC-3
mounting supportPlate
standardsIEC 60947-1
JIS C8201-4-1
EN 60947-4-1
EN 60947-1
IEC 60947-4-1
product certificationsABS
UL
CCC
CSA
RMRoS
CB
connections - terminalsControl circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end
Power circuit: bar 2 cable(s) - busbar cross section: 60 x 5 mm
Power circuit: bolted connection
tightening torqueControl circuit: 1.2 N.m
Power circuit: 58 N.m
control circuit voltage limitsOperational: 0.85...1.1 Uc (at 55 °C)
Drop-out: 0.3...0.5 Uc (at 55 °C)
inrush power in W1900 W (at 20 °C)
hold-in power consumption in W12 W at 20 °C
heat dissipation12 W
operating time40...50 ms opening
60...80 ms closing
mechanical durability5 Mcycles
maximum operating rate600 cyc/h 55 °C
compatibility codeLC1F
motor power range250…500 kW at 200…240 V 3 phases
250…500 kW at 380…440 V 3 phases
110…220 kW at 200…240 V 3 phases
250…500 kW at 480…500 V 3 phases
motor starter typeDirect on-line contactor
contactor coil voltage220 V DC standard
230 V DC standard
220 V AC standard
230 V AC standard
240 V AC standard
Environment
IP degree of protectionIP20 front face with shrouds conforming to IEC 60529
IP20 front face with shrouds conforming to VDE 0106
protective treatmentTH
ambient air temperature for operation-5…55 °C
ambient air temperature for storage-60…80 °C
permissible ambient air temperature around the device-5…55 °C
height304 mm
width309 mm
depth255 mm
net weight18.75 kg

Dimensions

Dimension LC1F800

Auxiliaries and accessories for LC1F800MW

Similar or replacement products LC1F800MW