Motor Circuit Breaker TeSys GV3L80

  • Model:
    003.002.199
  • Copy
Motor Circuit Breaker GV3L80
Manufacturer: Schneider Electric
Barcode: 3606481304575
The TeSys GV3L80 circuit breaker is designed for the protection and control of 45kW electric motors (at 400…415Vac 50/60Hz).
The switch combines the following functions:
  • short circuit and overload protection
  • motor on / off control
  • contact position indication
Main characteristics:
  • electromagnetic release
  • rating of electromagnetic protection - 80A

Main

rangeTeSys
TeSys Deca
product nameTeSys GV3
TeSys Deca
product or component typeCircuit breaker
device short nameGV3L
device applicationMotor
poles description3P
network typeAC
utilisation categoryCategory A conforming to IEC 60947-2
AC-3 conforming to IEC 60947-4-1
network frequency50/60 Hz
breaking capacity50 kA Icu at 440 V AC 50/60 Hz
12 kA Icu at 500 V AC 50/60 Hz
6 kA Icu at 690 V AC 50/60 Hz
50 kA Icu at 400/415 V AC 50/60 Hz
65 kA Icu at 230/240 V AC 50/60 Hz
[Ics] rated service short-circuit breaking capacity100 % at 230/240 V AC 50/60 Hz
50 % at 500 V AC 50/60 Hz
50 % at 690 V AC 50/60 Hz
60 % at 400/415 V AC 50/60 Hz
60 % at 440 V AC 50/60 Hz
trip unit technologyMagnetic
magnetic tripping current1120 A

Complementary

fixing mode35 mm symmetrical DIN rail: clipped
Panel: screwed (with 3 x M4 screws)
operating positionAny position, no direct mounting with contactor, use cable length > 10 cm
Any position, do not use with accessory GV3S
motor power kW45 kW at 400/415 V AC 50/60 Hz maximum peak current 750 A
55 kW at 690 V AC 50/60 Hz maximum peak current 750 A
45 kW at 500 V AC 50/60 Hz maximum peak current 750 A
control typeRotary knob
[Ue] rated operational voltage690 V AC 50/60 Hz conforming to IEC 60947-2
[Ui] rated insulation voltage690 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage6 kV conforming to IEC 60947-2
power dissipation per pole8 W
mechanical durability50000 cycles
electrical durability20000 cycles for AC-3 at 415 V In
maximum operating rate25 cyc/h
connections - terminalsEverLink BTR screw connectors 1 cable(s) 1…35 mm² solid
EverLink BTR screw connectors 2 cable(s) 1…25 mm² solid
EverLink BTR screw connectors 1 cable(s) 1…35 mm² flexible with cable end
EverLink BTR screw connectors 2 cable(s) 1…25 mm² flexible with cable end
EverLink BTR screw connectors 1 cable(s) 1…35 mm² flexible
EverLink BTR screw connectors 2 cable(s) 1…25 mm² flexible
tightening torque5 N.m on EverLink BTR screw connectors for cable 25 mm²
8 N.m on EverLink BTR screw connectors for cable 35 mm²
mechanical robustnessShocks: 30 Gn for 11 ms opened conforming to IEC 60068-2-27
Vibrations: 4 Gn, 5…300 Hz conforming to IEC 60068-2-6
Shocks: 5 Gn for 11 ms closed conforming to IEC 60068-2-27
suitability for isolationYes conforming to IEC 60947-1
height132 mm
width55 mm
depth136 mm
product weight0.96 kg
colourGrey (SE GREY 6)
Green (SE GREEN 2)

Environment

standardsEN/IEC 60947-2
EN/IEC 60947-4-1
product certificationsIECEE CB Scheme
CCC
EAC
ABS
LROS (Lloyds register of shipping)
DNV-GL
BV
UKCA
protective treatmentTH
IP degree of protectionIP20 conforming to IEC 60529
IK degree of protectionIK09
ambient air temperature for operation-20…60 °C
ambient air temperature for storage-40…80 °C
fire resistance960 °C conforming to IEC 60695-2-1
operating altitude0…3000 m

Dimension

Dimensions of the circuit breaker GV3L series
Electrical clearance X1=40mm for Ue≤ 500V
and X1=50mm for Ue≤ 690V

Scheme

Electrical scheme of the circuit breaker GV3L series

Auxiliaries and accessories for GV3L80

background
GVAN20
 
 
background
GVAN11
 
 
background
GVAE11
 
 