Contactor LC1BM33P22

Model: 004.013.006
Contactor LC1BM33P22
Manufacturer: Schneider Electric
Barcode: 3389110541236
The B-line contactors offer proven performance for resistive loads or large motor starting applications such as fans, crushers, pumps, compressors and overhead cranes. They offer high reliability with long mechanical and electrical life and the most complete line of accessories in the industry.
Price by call

Main

rangeTeSys
product nameTeSys B
product or component typeContactor
device short nameLC1BM
contactor applicationMotor-heating-lighting
utilisation categoryAC-3
AC-1
control circuit typeAC
coil typeStandard
poles description3P
pole contact composition3 NO
[Ie] rated operational current1250 A (at < 40 °C) AC AC-1 for power circuit
1000 A (at < 55 °C) AC AC-3 for power circuit
motor power kW530 kW at 1000 V AC 50/60 Hz (AC-3)
160 kW at 400 V AC 50/60 Hz (AC-4)
280 kW at 220...230 V AC 50/60 Hz (AC-3)
500 kW at 380...400 V AC 50/60 Hz (AC-3)
530 kW at 415 V AC 50/60 Hz (AC-3)
560 kW at 440 V AC 50/60 Hz (AC-3)
600 kW at 500 V AC 50/60 Hz (AC-3)
670 kW at 660...690 V AC 50/60 Hz (AC-3)
auxiliary contact composition2 NO + 2 NC
[Uc] control circuit voltage230 V AC 50...400 Hz

Complementary

control circuit voltage limitsDrop-out: 0.3...0.5 Uc at 50...400 Hz
Operational: 0.85...1.1 Uc at 50...400 Hz
[Ui] rated insulation voltage1000 V - for power circuit conforming to IEC 60158-1
1000 V - for power circuit conforming to IEC 60947-4
1500 V - for power circuit conforming to VDE 0110 group C
mounting modeFixed
mounting supportNotched mounting rails
Bar support bracket
tightening torquePower circuit: 35 N.m - on bars
[Ue] rated operational voltagePower circuit: ≤ 1000 V AC 50/60 Hz
[Ith] conventional free air thermal current1250 A (at 40 °C) for power circuit
Irms rated making capacity10000 A at 1000 V AC for power circuit conforming to IEC 60158-1
10000 A at 1000 V AC for power circuit conforming to IEC 60947-4
rated breaking capacity10000 A at 440 V for power circuit conforming to IEC 60158-1
10000 A at 440 V for power circuit conforming to IEC 60947-4
4000 A at 1000 V for power circuit conforming to IEC 60158-1
4000 A at 1000 V for power circuit conforming to IEC 60947-4
8000 A at 660...690 V for power circuit conforming to IEC 60158-1
8000 A at 660...690 V for power circuit conforming to IEC 60947-4
9000 A at 500 V for power circuit conforming to IEC 60158-1
9000 A at 500 V for power circuit conforming to IEC 60947-4
associated fuse rating1200 A aM at ≤ 440 V for power circuit
1200 A gI at ≤ 440 V for power circuit
1500 A gI at ≤ 440 V for power circuit
average impedance0.18 mOhm - Ith 1250 A 50 Hz for power circuit
power dissipation per pole180 W AC-3 - Ith 1250 A
280 W AC-1 - Ith 1250 A
inrush power in VA1300 VA
hold-in power consumption in VA31 VA 50/60 Hz
operating time100...150 ms closing
50...100 ms opening
mechanical durability1200000 cycles
maximum operating rate120 cyc/h 55 °C
height490 mm
width570 mm
depth475 mm
net weight57 kg

Environment

standardsVDE 0660
IEC 60158-1
BS 5424
IEC 60947-4
NF C 63-110
product certificationsBV
CSA
RINA
protective treatmentTC
TH
ambient air temperature for operation-5…55 °C
ambient air temperature for storage-60…80 °C
operating altitude3000 m without derating

Auxiliaries and accessories for LC1BM33P22

Similar or replacement products LC1BM33P22