| Main |
|---|
| range | TeSys |
| product name | TeSys F |
| product or component type | Contactor |
| device short name | LC1F |
| contactor application | Resistive load Motor control |
| utilisation category | AC-3 AC-4 AC-1 |
| poles description | 3P |
| power pole contact composition | 3 NO |
| [Ue] rated operational voltage | ≤ 460 V DC ≤ 690 V AC 50/60 Hz |
| [Ie] rated operational current | 315 A (at < 40 °C) at ≤ 440 V AC-1 225 A (at < 55 °C) at ≤ 440 V AC-3 |
| motor power kW | 110 kW at 380…400 V AC 50/60 Hz (AC-3) 110 kW at 415 V AC 50/60 Hz (AC-3) 110 kW at 440 V AC 50/60 Hz (AC-3) 129 kW at 500 V AC 50/60 Hz (AC-3) 129 kW at 660…690 V AC 50/60 Hz (AC-3) 63 kW at 220…230 V AC 50/60 Hz (AC-3) 40 kW at 400 V AC 50/60 Hz (AC-4) |
| [Uc] control circuit voltage | 220 V DC |
| coil type | Standard |
| Complementary |
|---|
| [Uimp] rated impulse withstand voltage | 8 kV |
| overvoltage category | III |
| [Ith] conventional free air thermal current | 315 A (at 40 °C) |
| rated breaking capacity | 1800 A conforming to IEC 60947-4-1 |
| [Icw] rated short-time withstand current | 1800 A 40 °C - 10 s 1000 A 40 °C - 30 s 850 A 40 °C - 1 min 560 A 40 °C - 3 min 440 A 40 °C - 10 min |
| associated fuse rating | 315 A gG at ≤ 440 V 250 A aM at ≤ 440 V |
| average impedance | 0.32 mOhm - Ith 315 A 50 Hz |
| [Ui] rated insulation voltage | 1000 V conforming to IEC 60947-4-1 1500 V conforming to VDE 0110 group C |
| power dissipation per pole | 32 W AC-1 16 W AC-3 |
| mounting support | Plate |
| standards | IEC 60947-4-1 JIS C8201-4-1 EN 60947-4-1 EN 60947-1 IEC 60947-1 |
| product certifications | DNV UL RINA RMRoS LROS (Lloyds register of shipping) CSA CB ABS BV |
| connections - terminals | Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end Power circuit: bar 2 cable(s) - busbar cross section: 32 x 4 mm Power circuit: lugs-ring terminals 1 cable(s) 185 mm² Power circuit: connector 1 cable(s) 185 mm² Power circuit: bolted connection |
| tightening torque | Control circuit: 1.2 N.m Power circuit: 35 N.m |
| control circuit voltage limits | Operational: 0.85…1.1 Uc (at 55 °C) Drop-out: 0.15…0.2 Uc (at 55 °C) |
| inrush power in W | 800 W (at 20 °C) |
| hold-in power consumption in W | 5 W at 20 °C |
| heat dissipation | 5 W |
| operating time | 30…40 ms closing 30…50 ms opening |
| mechanical durability | 10 Mcycles |
| maximum operating rate | 2400 cyc/h 55 °C |
| compatibility code | LC1F |
| motor power range | 55…100 kW at 200…240 V 3 phases 110…220 kW at 480…500 V 3 phases 110…220 kW at 380…440 V 3 phases |
| motor starter type | Direct on-line contactor |
| contactor coil voltage | 220 V DC standard |
| Environment |
|---|
| IP degree of protection | IP20 front face with shrouds conforming to IEC 60529 IP20 front face with shrouds conforming to VDE 0106 |
| protective treatment | TH |
| ambient air temperature for operation | -5…55 °C |
| ambient air temperature for storage | -60…80 °C |
| permissible ambient air temperature around the device | -40…70 °C |
| height | 197 mm |
| width | 168.5 mm |
| depth | 181 mm |
| net weight | 4.75 kg |