| [Uc] control circuit voltage | 48…1000 V AC 40…400 Hz with LX1/LX9 coil 48…440 V DC with LX4 coil 100…250 V AC 50/60 Hz with LXE coil 100…380 V DC with LXE coil |
| [Uimp] rated impulse withstand voltage | 8 kV |
| overvoltage category | III |
| [Ith] conventional free air thermal current | 500 A (at 40 °C) |
| Irms rated making capacity | 4000 A AC conforming to IEC 60947-4-1 |
| rated breaking capacity | 3200 A conforming to IEC 60947-4-1 |
| [Icw] rated short-time withstand current | 3600 A 40 °C - 10 s 2400 A 40 °C - 30 s 1700 A 40 °C - 1 min 1200 A 40 °C - 3 min 1000 A 40 °C - 10 min |
| associated fuse rating | 400 A aM at ≤ 440 V 500 A gG at ≤ 440 V |
| average impedance | 0.26 mOhm - Ith 500 A 50 Hz |
| [Ui] rated insulation voltage | 1000 V conforming to IEC 60947-4-1 1500 V conforming to VDE 0110 group C |
| power dissipation per pole | 65 W AC-1 42 W AC-3 |
| control circuit voltage limits | Operational: 0.85…1.1 Uc AC 40…400 Hz with LX1/LX9 coil Drop-out: 0.3…0.5 Uc AC 40…400 Hz with LX1/LX9 coil Operational: 0.85…1.1 Uc DC with LX4 coil Drop-out: 0.2…0.35 Uc DC with LX4 coil Operational: 85…275 V AC 50/60 Hz with LXE coil Drop-out: 0…60 V AC 50/60 Hz with LXE coil Operational: 85…418 V DC with LXE coil Drop-out: 0…45 V DC with LXE coil |
| heat dissipation | 14 W 2.2…5.5 W |
| operating time | 40…75 ms closing for with LX1/LX9 coil 100…170 ms opening for with LX1/LX9 coil 50…60 ms closing for with LX4 coil 45…60 ms opening for with LX4 coil 40…80 ms closing for with LXE coil 6…54 ms opening for with LXE coil |
| mounting support | Plate |
| standards | JIS C8201-4-1 IEC 60947-4-1 IEC 60947-1 EN 60947-4-1 EN 60947-1 |
| product certifications | CB ABS DNV RMRoS LROS (Lloyds register of shipping) BV RINA UL CSA |
| connections - terminals | Power circuit: bar 2 cable(s) - busbar cross section: 30 x 5 mm Power circuit: lugs-ring terminals 2 cable(s) 150 mm² Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible with cable end Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²solid without cable end Control circuit: screw clamp terminals 1 cable(s) 1…4 mm² Control circuit: screw clamp terminals 2 cable(s) 1…4 mm² Control circuit: screw clamp terminals 1.0 cable(s) 0.2…2.5 mm²flexible without cable end Control circuit: screw clamp terminals 1.0 cable(s) 0.25…2.5 mm²flexible with cable end Control circuit: screw clamp terminals 1.0 cable(s) 0.2…2.5 mm²solid without cable end |
| tightening torque | Power circuit: 35 N.m Control circuit: 1.2 N.m Control circuit: 0.6 N.m |
| mechanical durability | 10 Mcycles |
| inrush power in VA | 1000…1150 VA, 40…400 Hz cos phi 0.9 (at 20 °C)with LX1/LX9 coil 920…1140 VA (at 20 °C)with LX4 coil 360…470 VA, 50/60 Hz cos phi 0.5 (at 20 °C)with LXE coil 410…450 VA (at 20 °C)with LXE coil |
| hold-in power consumption in VA | 12…18 VA, 40…400 Hz cos phi 0.9 (at 20 °C)with LX1/LX9 coil 4…7.5 VA (at 20 °C)with LX4 coil 4.5…7.0 VA, 50/60 Hz cos phi 0.5 (at 20 °C)with LXE coil 2.5…4.0 VA (at 20 °C)with LXE coil |
| maximum operating rate | 2400 cyc/h 55 °C |
| compatibility code | LC1F |