Relay CA2KN40M7

Model: 005.005.001
Relay CA2KN40M7
Manufacturer: Schneider Electric
Barcode: 3389110500332
Price by call

Main

rangeTeSys
product nameTeSys CAK
product or component typeControl relay
device short nameCA2K
contactor applicationControl circuit
utilisation categoryAC-15
DC-13
pole contact composition4 NO
[Ue] rated operational voltage≤ 690 V ≤ 400 Hz
control circuit typeAC at 50/60 Hz
[Uc] control circuit voltage220...230 V AC 50/60 Hz

Complementary

[Ith] conventional free air thermal current10 A (at 50 °C)
Irms rated making capacity110 A conforming to IEC 60947
associated fuse rating10 A gG conforming to IEC 60947
10 A gG conforming to VDE 0660
[Ui] rated insulation voltage690 V conforming to IEC 60947
750 V conforming to VDE 0110 group C
690 V conforming to BS 5424
600 V conforming to CSA C22.2 No 14
mounting supportPlate
Rail
connections - terminalsScrew clamp terminals 1 cable(s) 1.5…4 mm²solid
Screw clamp terminals 2 cable(s) 1.5…4 mm²solid
Screw clamp terminals 1 cable(s) 0.75…4 mm²flexible with cable end
Screw clamp terminals 2 cable(s) 0.75…4 mm²flexible without cable end
Screw clamp terminals 1 cable(s) 0.34…1.5 mm²flexible with cable end
Screw clamp terminals 2 cable(s) 0.34…1.5 mm²flexible without cable end
tightening torque1.3 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
1.3 N.m - on screw clamp terminals - with screwdriver Philips No 26 mm
control circuit voltage limitsDrop-out: 0.2...0.75 Uc (at < 50 °C)
Operational: 0.8...1.15 Uc (at < 50 °C)
operating time10...20 ms coil de-energisation and NO opening
10...20 ms coil energisation and NO closing
mechanical durability10 Mcycles
maximum operating rate10000 cyc/h
immunity to microbreaks2 ms
inrush power in VA30 VA (at 20 °C)
hold-in power consumption in VA4.5 VA (at 20 °C)
heat dissipation1.3 W
minimum switching voltage17 V
minimum switching current5 mA
non overlap distance0.5 mm
insulation resistance> 10 MOhm
height58 mm
width45 mm
depth57 mm
net weight0.18 kg

Environment

standardsBS 5424
IEC 60947
NF C 63-140
VDE 0660
product certificationsCSA
UL
IP degree of protectionIP2x
protective treatmentTC conforming to IEC 60068
ambient air temperature for operation-25…50 °C
ambient air temperature for storage-50…80 °C
operating altitude2000 m without derating
flame retardanceV1 conforming to UL 94
Requirement 2 conforming to NF F 16-101
Requirement 2 conforming to NF F 16-102
mechanical robustnessVibrations contactor open: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6
Shocks contactor open: 10 Gn for 11 ms conforming to IEC 60068-2-27
Shocks contactor closed: 15 Gn for 11 ms conforming to IEC 60068-2-27

Auxiliaries and accessories for CA2KN40M7

Similar or replacement products CA2KN40M7