Miniature relay RXM2AB2P7

  • Model:
    005.006.001
  • Copy
Miniature relay RXM2AB2P7
Manufacturer: Schneider Electric
Barcode: 3389119403535
Miniature electromagnetic relay Zelio Relay RXM2AB2P7.
On the front panel are located:
- Button for testing the contacts;
- Label for marking relays;
- LED status indicator relay.
The relay has 2 (2CO) contacts. Material of contacts is AgNi.
Coil - 230V 50/60Hz.

Main

Range of productHarmony Electromechanical Relays
Series nameMiniature
Product or component typePlug-in relay
device short nameRXM
contacts type and composition2 C/O
[Uc] control circuit voltage230 V AC 50/60 Hz
Status LEDWith
control typeLockable test button
Utilisation coefficient20 %

Complementary

Shape of pinFlat
[Ui] rated insulation voltage250 V conforming to IEC
300 V conforming to CSA
300 V conforming to UL
[Uimp] rated impulse withstand voltage4 kV during 1.2/50 µs
contacts materialAgNi
[Ie] rated operational current12 A at 28 V (DC) NO conforming to IEC
12 A at 250 V (AC) NO conforming to IEC
6 A at 28 V (DC) NC conforming to IEC
6 A at 250 V (AC) NC conforming to IEC
12 A at 28 V (DC) conforming to UL
12 A at 277 V (AC) conforming to UL
Continuous output current10 A
Maximum switching voltage250 V conforming to IEC
resistive rated load12 A at 250 V AC
12 A at 28 V DC
Maximum switching capacity3000 VA/336 W
Minimum switching capacity170 mW at 10 mA, 17 V
Operating rate<= 1200 cycles/hour under load
<= 18000 cycles/hour no-load
Mechanical durability10000000 cycles
Electrical durability100000 cycles for resistive load
average coil consumption in VA1.2 at 60 Hz
Average consumption1.2 VA at 60 Hz
Drop-out voltage threshold>= 0.15 Uc
operate time20 ms
release time20 ms
average coil resistance15000 Ohm at 20 °C +/- 15 %
Rated operational voltage limits184…253 V AC
Safety reliability dataB10d = 100000
Protection categoryRT I
Test levelsLevel A group mounting
Operating positionAny position
CAD overall height82.8 mm
CAD overall depth80.35 mm
Net weight0.037 kg
device presentationComplete product

Environment

Dielectric strength1300 V AC between contacts with micro disconnection
2000 V AC between coil and contact with basic insulation
2000 V AC between poles with basic insulation
product certificationsCSA
GOST
UL
CE
Lloyd's
StandardsEN/IEC 61810-1
UL 508
CSA C22.2 No 14
Ambient air temperature for storage-40…85 °C
Ambient air temperature for operation-40…55 °C
Vibration resistance3 gn, amplitude = +/- 1 mm (f = 10…150 Hz)5 cycles in operation
5 gn, amplitude = +/- 1 mm (f = 10…150 Hz)5 cycles not operating
IP degree of protectionIP40 conforming to EN/IEC 60529
Shock resistance10 gn for in operation
30 gn for not operating
Pollution degree3

Relay dimensions and wiring diagram

Dimensions and wiring diagram

Сайт использует рекомендательные технологии и файлы cookie