Circuit breaker iC60H A9F89316 3P 16A C

Model: 003.013.148
Circuit breaker iC60H A9F89316
Manufacturer: Schneider Electric
Barcode: 3606480095122
Circuit breaker iC60H A9F89316 is used for protection of cables against overloads and short-circuits in final distribution
$119.82
 pcs

Main

device applicationDistribution
rangeActi 9
product nameActi 9 iC60
product or component typeMiniature circuit-breaker
device short nameIC60H
poles description3P
number of protected poles3
[In] rated current16 A
network typeAC
DC
trip unit technologyThermal-magnetic
curve codeC
breaking capacity10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
42 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2
10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
15 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2
30 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2
42 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2
15 kA Icu at ≤ 180 V DC conforming to EN/IEC 60947-2
utilisation categoryCategory A conforming to EN 60947-2
Category A conforming to IEC 60947-2
suitability for isolationYes conforming to EN 60898-1
Yes conforming to EN 60947-2
Yes conforming to IEC 60898-1
Yes conforming to IEC 60947-2
standardsIEC 60947-2
EN 60947-2
EN 60898-1
IEC 60898-1

Complementary

network frequency50/60 Hz
magnetic tripping limit8 x In +/- 20 %
[Ics] rated service breaking capacity15 kA 50 % conforming to EN 60947-2 - 220...240 V AC 50/60 Hz
7.5 kA 50 % conforming to EN 60947-2 - 380...415 V AC 50/60 Hz
5 kA 50 % conforming to EN 60947-2 - 440 V AC 50/60 Hz
15 kA 50 % conforming to IEC 60947-2 - 220...240 V AC 50/60 Hz
7.5 kA 50 % conforming to IEC 60947-2 - 380...415 V AC 50/60 Hz
5 kA 50 % conforming to IEC 60947-2 - 440 V AC 50/60 Hz
7500 A 75 % conforming to EN 60898-1 - 400 V AC 50/60 Hz
7500 A 75 % conforming to IEC 60898-1 - 400 V AC 50/60 Hz
21 kA 50 % conforming to IEC 60947-2 - 12...133 V AC 50/60 Hz
21 kA 50 % conforming to EN 60947-2 - 12...133 V AC 50/60 Hz
15 kA 100 % conforming to IEC 60947-2 - 125...180 V DC
15 kA 100 % conforming to EN 60947-2 - 125...180 V DC
limitation class3 conforming to EN 60898-1
3 conforming to IEC 60898-1
[Ui] rated insulation voltage500 V AC 50/60 Hz conforming to EN 60947-2
500 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage6 kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2
contact position indicatorYes
control typeToggle
local signallingTrip indicator
mounting modeFixed
mounting supportDIN rail
comb busbar and distribution block compatibilityTop or bottom: YES
9 mm pitches6
height85 mm
width54 mm
depth78.5 mm
net weight0.375 kg
colourWhite
mechanical durability20000 cycles
electrical durability10000 cycles
connections - terminalsSingle terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexible
wire stripping length14 mm for top or bottom connection
tightening torque2 N.m top or bottom
earth-leakage protectionSeparate block

Environment

IP degree of protectionIP20 conforming to IEC 60529
IP20 conforming to EN 60529
pollution degree3 conforming to EN 60947-2
3 conforming to IEC 60947-2
overvoltage categoryIV
tropicalisation2 conforming to IEC 60068-1
relative humidity95 % at 55 °C
operating altitude0...2000 m
ambient air temperature for operation-35…70 °C
ambient air temperature for storage-40…85 °C

Dimension

Dimension circuit breaker iC60H 3P

Schneider Electric nomenclature of iC60H circuit breakers

Poles 1 2 3 4
Rated current, A Curves
B C D B C D B C D B C D
0.5 A9F83170 A9F84170 A9F85170 A9F83270 A9F84270 A9F85270 A9F83370 A9F84370 A9F85370 A9F83470 A9F84470 A9F85470
1 A9F83101 A9F84101 A9F85101 A9F83201 A9F84201 A9F85201 A9F83301 A9F84301 A9F85301 A9F83401 A9F84401 A9F85401
2 A9F83102 A9F84102 A9F85102 A9F83202 A9F84202 A9F85202 A9F83302 A9F84302 A9F85302 A9F83402 A9F84402 A9F85402
3 A9F83103 A9F84103 A9F85103 A9F83203 A9F84203 A9F85203 A9F83303 A9F84303 A9F85303 A9F83403 A9F84403 A9F85403
4 A9F83104 A9F84104 A9F85104 A9F83204 A9F84204 A9F85204 A9F83304 A9F84304 A9F85304 A9F83404 A9F84404 A9F85404
6 A9F88106 A9F89106 A9F85106 A9F88206 A9F89206 A9F85206 A9F88306 A9F89306 A9F85306 A9F88406 A9F89406 A9F85406
10 A9F88110 A9F89110 A9F85110 A9F88210 A9F89210 A9F85210 A9F88310 A9F89310 A9F85310 A9F88410 A9F89410 A9F85410
13 A9F83113 A9F84113 A9F85113 A9F83213 A9F84213 A9F85213 A9F83313 A9F84313 A9F85313 A9F83413 A9F84413 A9F85413
16 A9F88116 A9F89116 A9F85116 A9F88213 A9F89216 A9F85216 A9F88316 A9F89316 A9F85316 A9F88416 A9F89416 A9F85416
20 A9F88120 A9F89120 A9F85120 A9F88220 A9F89220 A9F85220 A9F88320 A9F89320 A9F85320 A9F88420 A9F89420 A9F85420
25 A9F88125 A9F89125 A9F85125 A9F88225 A9F89225 A9F85225 A9F88325 A9F89325 A9F85325 A9F88425 A9F89425 A9F85425
32 A9F88132 A9F89132 A9F85132 A9F88232 A9F89232 A9F85232 A9F88332 A9F89332 A9F85332 A9F88432 A9F89432 A9F85432
40 A9F88140 A9F89140 A9F85140 A9F88240 A9F89240 A9F85240 A9F88340 A9F89340 A9F85340 A9F88440 A9F89440 A9F85440
50 A9F88150 A9F89150 A9F85150 A9F88250 A9F89250 A9F85250 A9F88350 A9F89350 A9F85350 A9F88450 A9F89450 A9F85450
63 A9F88163 A9F89163 A9F85163 A9F88263 A9F89263 A9F85263 A9F88363 A9F89363 A9F85363 A9F88463 A9F89463 A9F85463

Auxiliaries and accessories for A9F89316

Similar or replacement products A9F89316