18780 NG125L 1P 25A C

Model: 003.014.013
18780 NG125L 1P 25A C
Manufacturer: Schneider Electric
Barcode: 3303430187806
Circuit breaker is used for protection of cables against overloads and short-circuits in final distribution.
Rated current - 25A;
Characteristic Trip Curves - C.
Price by call

Main

range of productNG125
rangeActi 9
product nameActi 9 NG125
product or component typeMiniature circuit-breaker
device short nameNG125L
device applicationDistribution
poles description1P
number of protected poles1
[In] rated current25 A at 40 °C
network typeAC
DC
trip unit technologyThermal-magnetic
curve codeC
breaking capacity50 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2
100 kA Icu at 110...130 V AC 50/60 Hz conforming to EN/IEC 60947-2
50 kA Icu at 12 V DC conforming to EN/IEC 60947-2
50 kA Icu at 125 V DC conforming to EN/IEC 60947-2
36 kA Icu at ≤ 144 V DC conforming to EN/IEC 60947-2
12.5 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2
utilisation categoryCategory A conforming to IEC 60947-2
suitability for isolationYes conforming to IEC 60947-2

Complementary

network frequency50/60 Hz
[Ue] rated operational voltage380...415 V AC 50/60 Hz
125 V DC
≤ 144 V DC
12 V DC
220...240 V AC 50/60 Hz
110...130 V AC 50/60 Hz
magnetic tripping limit8 x In +/- 20 %
[Ics] rated service breaking capacity37.5 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz
75 kA 75 % conforming to EN/IEC 60947-2 - 110...130 V AC 50/60 Hz
9.37 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz
50 kA 100 % conforming to EN/IEC 60947-2 - 60 V DC
50 kA 100 % conforming to EN/IEC 60947-2 - 125 V DC
[Ui] rated insulation voltage690 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage8 kV conforming to EN/IEC 60947-2
contact position indicatorYes
control typeToggle
Manual tripping test
local signallingON/OFF indication
Trip indicator
mounting modeClip-on
mounting support35 mm symmetrical DIN rail
comb busbar and distribution block compatibilityYES
9 mm pitches3
height103 mm
width27 mm
depth81 mm
net weight0.24 kg
mechanical durability20000 cycles
electrical durability10000 cycles
provision for padlockingPadlockable
locking options descriptionIntegrated padlocking
connections - terminalsTunnel type terminals1.5…50 mm² rigid
Tunnel type terminals1…35 mm² flexible
wire stripping length20 mm
tightening torque3.5 N.m
earth-leakage protectionWithout

Environment

standardsEN/IEC 60947-2
IP degree of protectionIP20 conforming to IEC 60529
IK degree of protectionIK05 conforming to EN/IEC 62262
pollution degree3 conforming to IEC 60947-2
overvoltage categoryIV
tropicalisation2 conforming to IEC 60068-1
relative humidity95 % at 55 °C
operating altitude2000 m
ambient air temperature for operation-30…70 °C
ambient air temperature for storage-40…70 °C

Dimension

Dimension breaker NG125L 1P

Auxiliaries and accessories for 18780

Similar or replacement products 18780