Thermal-magnetic motor circuit breaker GV2ME32

Model: 003.002.082
Thermal-magnetic motor circuit breaker GV2ME32
Manufacturer: Schneider Electric
Barcode: 3389110343298
Thermal-magnetic motor circuit breakers GV2ME32 with screw terminals.
Price by call

Specification

Technical characteristics
Number of poles3
Trip element typethermal-magnetic
Utilisation categoryA conforming to IEC 60947-2
AC-3 conforming to IEC 60947-4-1
Rated operational voltage (Ue)690VAC, 50/60Hz conforming to IEC 60947-2
Rated voltage600VAC, 50/60Hz confroming to CSA C22-2 #14, conforming to UL 508
Rated insulation voltage (Ui)690V conforming to 60947-2
Rated impulse withstand voltage (Uimp)6kV conforming to IEC 60947-2
Total power dissipated per pole2,5W
Motor power15kW at 400...415VAC
18,5kW at 500VAC
22kW at 690VAC
Max conventional rated thermal current (Ith)32A conforming to IEC 60947-4-1
Rated current (In)32A
Tripping current range24...32A conforming to IEC 60947-4-1
Tripping threshold of magnetic elements416A
Breaking capacity (Icu)50kA at 230...240V
10kA at 400...415V
6kA at 440V
4kA at 500V
3kA at 690V
Rated breaking current (Ics)100% of Icu at 230...240V
50% of Icu at 400...415V
50% of Icu at 440V
75% of Icu at 500V
75% of Icu at 690V
Mechanical durability100 000 cycles
Electrical durability for AC-3 duty (440V, In/2)100 000 cycles
Duty class (Max operating rate)25 cycles/h
Rated dutycontinuous duty
Environmental characteristics
Degree of protectionIP20 conforming to IEC 60529
Ambient operating temperature-20°C...+60°C (open mounted)
-20°C...+40°C (in enclosure)
Storage temperature-40°C...+80°C
Flame resistance960°C conforming to IEC 60695-2-1
Max operating altitude≤ 2000m
Shock resistance30gn - 11ms conforming to IEC 60068-2-27
Vibration resistance5gn (50...150Hz) conforming to IEC 60068-2-6
Sensitivity to phase failureyes conforming to IEC 60947-4-1
Resistance to mechanical impact0,5J
Mounting characteristics
Operating positionvertical mounting
Mountingon a panel or 35mm DIN rail
Connection to screw clamp terminals2×1...6mm2 solid cable
2×1,5...6mm2 flexible cable without cable end
2×1...4mm2 flexible cable with cable end
Tightening torque1,7N·m
Connection to spring terminals2×1...6mm2 solid cable
2×1,5...4mm2 flexible cable without cable end

Dimensions

Basic dimensions
Electrical clearance X1=40mm for Ue≤ 690V

Scheme

Electrical scheme

Thermal-magnetic tripping curves

Average operating times at 20°C related to multiples of the setting current
Tripping curves

Auxiliaries and accessories for GV2ME32

background
GV2AF3
 
 

Similar or replacement products GV2ME32