Contactor LC1F500M7

Model: 004.007.023
Contactor LC1F500M7
Manufacturer: Schneider Electric
Barcode: 3389110227062
The F-line contactors offer proven performance for resistive loads or large motor starting applications such as fans, crushers, pumps, compressors and overhead cranes. They offer high reliability with long mechanical and electrical life and the most complete line of accessories in the industry.
Price by call
Main
rangeTeSys
product nameTeSys F
product or component typeContactor
device short nameLC1F
contactor applicationMotor control
Resistive load
utilisation categoryAC-1
AC-4
AC-3
poles description3P
power pole contact composition3 NO
[Ue] rated operational voltage≤ 1000 V AC 50/60 Hz
≤ 460 V DC
[Ie] rated operational current700 A (at < 40 °C) at ≤ 440 V AC AC-1
500 A (at < 55 °C) at ≤ 440 V AC AC-3
motor power kW250 kW at 380...400 V AC 50/60 Hz (AC-3)
280 kW at 415 V AC 50/60 Hz (AC-3)
295 kW at 440 V AC 50/60 Hz (AC-3)
355 kW at 500 V AC 50/60 Hz (AC-3)
335 kW at 660...690 V AC 50/60 Hz (AC-3)
335 kW at 1000 V AC 50/60 Hz (AC-3)
147 kW at 220...230 V AC 50/60 Hz (AC-3)
80 kW at 400 V AC 50/60 Hz (AC-4)
[Uc] control circuit voltage220 V AC 40...400 Hz
Complementary
[Uimp] rated impulse withstand voltage8 kV
overvoltage categoryIII
[Ith] conventional free air thermal current700 A (at 40 °C)
rated breaking capacity4000 A conforming to IEC 60947-4-1
[Icw] rated short-time withstand current4200 A 40 °C - 10 s
3200 A 40 °C - 30 s
2400 A 40 °C - 1 min
1500 A 40 °C - 3 min
1200 A 40 °C - 10 min
associated fuse rating500 A aM at ≤ 440 V
800 A gG at ≤ 440 V
average impedance0.18 mOhm - Ith 700 A 50 Hz
[Ui] rated insulation voltage1000 V conforming to IEC 60947-4-1
1500 V conforming to VDE 0110 group C
power dissipation per pole88 W AC-1
45 W AC-3
mounting supportPlate
standardsEN 60947-4-1
IEC 60947-1
EN 60947-1
JIS C8201-4-1
IEC 60947-4-1
product certificationsCSA
CB
RMRoS
ABS
LROS (Lloyds register of shipping)
UL
RINA
BV
DNV
connections - terminalsControl circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end
Power circuit: bar 2 cable(s) - busbar cross section: 40 x 5 mm
Power circuit: lugs-ring terminals 2 cable(s) 240 mm²
Power circuit: bolted connection
tightening torqueControl circuit: 1.2 N.m
Power circuit: 35 N.m
control circuit voltage limitsOperational: 0.85...1.1 Uc 40...400 Hz (at 55 °C)
Drop-out: 0.3...0.5 Uc 40...400 Hz (at 55 °C)
inrush power in VA1100 VA 40...400 Hz cos phi 0.9 (at 20 °C)
hold-in power consumption in VA18 VA 40...400 Hz cos phi 0.9 (at 20 °C)
heat dissipation18 W
operating time40...65 ms closing
100...170 ms opening
mechanical durability10 Mcycles
maximum operating rate2400 cyc/h 55 °C
compatibility codeLC1F
motor power range250…500 kW at 380…440 V 3 phases
110…220 kW at 380…440 V 3 phases
110…220 kW at 200…240 V 3 phases
250…500 kW at 480…500 V 3 phases
motor starter typeDirect on-line contactor
contactor coil voltage220 V AC standard
Environment
IP degree of protectionIP20 front face with shrouds conforming to IEC 60529
IP20 front face with shrouds conforming to VDE 0106
protective treatmentTH
ambient air temperature for operation-5…55 °C
ambient air temperature for storage-60…80 °C
permissible ambient air temperature around the device-40…70 °C
height238 mm
width233 mm
depth232 mm
net weight11.35 kg

Auxiliaries and accessories for LC1F500M7

Similar or replacement products LC1F500M7

background
LC1F500P7
 
 
background
SQ0710-0015