[Uc] control circuit voltage | 110...400 V AC 40...400 Hz with LX1/LX9 coil 110...400 V DC with LX4 coil 100...250 V AC 50/60 Hz with LXE coil 100...380 V DC with LXE coil |
[Uimp] rated impulse withstand voltage | 8 kV |
overvoltage category | III |
[Ith] conventional free air thermal current | 1000 A (at 40 °C) |
Irms rated making capacity | 8000 A AC conforming to IEC 60947-4-1 |
rated breaking capacity | 6400 A conforming to IEC 60947-4-1 |
[Icw] rated short-time withstand current | 2600 A 40 °C - 3 min 5500 A 40 °C - 10 s 4600 A 40 °C - 30 s 3600 A 40 °C - 1 min 1700 A 40 °C - 10 min |
associated fuse rating | 1000 A gG at ≤ 440 V 800 A aM at ≤ 440 V |
average impedance | 0.12 mOhm - Ith 1000 A 50 Hz |
[Ui] rated insulation voltage | 1000 V conforming to IEC 60947-4-1 1500 V conforming to VDE 0110 group C |
power dissipation per pole | 120 W AC-1 77 W AC-3 |
control circuit voltage limits | Operational: 0.85...1.1 Uc AC 40...400 Hz with LX1/LX9 coil Drop-out: 0.3...0.5 Uc AC 40...400 Hz with LX1/LX9 coil Operational: 0.85...1.1 Uc DC with LX4 coil Drop-out: 0.3...0.5 Uc DC with LX4 coil Operational: 85...275 V AC 50/60 Hz with LXE coil Drop-out: 0...60 V AC 50/60 Hz with LXE coil Operational: 85...418 V DC with LXE coil Drop-out: 0...45 V DC with LXE coil |
heat dissipation | 25 W 2.2…5.5 W |
operating time | 60...80 ms closing for with LX1/LX9 coil 160...180 ms opening for with LX1/LX9 coil 60...80 ms closing for with LX4 coil 40...50 ms opening for with LX4 coil 40...80 ms closing for with LXE coil 6...54 ms opening for with LXE coil |
mounting support | Plate |
standards | IEC 60947-1 JIS C8201-4-1 EN 60947-1 IEC 60947-4-1 EN 60947-4-1 |
product certifications | CB CSA LROS (Lloyds register of shipping) ABS CCC UL |
connections - terminals | Power circuit: bar 2 cable(s) - busbar cross section: 60 x 5 mm Power circuit: bolted connection Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible with cable end Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²solid without cable end Control circuit: screw clamp terminals 1 cable(s) 1…4 mm² Control circuit: screw clamp terminals 2 cable(s) 1…4 mm² |
tightening torque | Power circuit: 58 N.m Control circuit: 1.2 N.m |
mechanical durability | 5 Mcycles |
inrush power in VA | 1700 VA, 40...400 Hz cos phi 0.9 (at 20 °C)with LX1/LX9 coil 1900 VA (at 20 °C)with LX4 coil 460…730 VA, 50/60 Hz cos phi 0.5 (at 20 °C)with LXE coil 500…680 VA cos phi 0.5 (at 20 °C)with LXE coil |
hold-in power consumption in VA | 12 VA, 40...400 Hz cos phi 0.9 (at 20 °C)with LX1/LX9 coil 12 VA (at 20 °C)with LX4 coil 7…10 VA, 50/60 Hz cos phi 0.5 (at 20 °C)with LXE coil 4.0…5.5 VA cos phi 0.5 (at 20 °C)with LXE coil |
maximum operating rate | 600 cyc/h 55 °C |
compatibility code | LC1F |