| Main |
|---|
| range | TeSys |
| product name | TeSys F |
| product or component type | Contactor |
| device short name | LC1F |
| contactor application | Motor control Resistive load |
| utilisation category | AC-4 AC-1 AC-3 |
| poles description | 3P |
| power pole contact composition | 3 NO |
| [Ue] rated operational voltage | ≤ 1000 V AC 50/60 Hz ≤ 460 V DC |
| [Ie] rated operational current | 1000 A (at < 40 °C) at ≤ 440 V AC AC-1 800 A (at < 55 °C) at ≤ 440 V AC AC-3 |
| motor power kW | 450 kW at 1000 V AC 50/60 Hz (AC-3) 450 kW at 500 V AC 50/60 Hz (AC-3) 475 kW at 660…690 V AC 50/60 Hz (AC-3) 110 kW at 400 V AC 50/60 Hz (AC-4) 450 kW at 380…400 V AC 50/60 Hz (AC-3) 450 kW at 415 V AC 50/60 Hz (AC-3) 450 kW at 440 V AC 50/60 Hz (AC-3) 250 kW at 220…230 V AC 50/60 Hz (AC-3) |
| [Uc] control circuit voltage | 220…230 V DC 220…240 V AC 40…400 Hz |
| coil type | Standard |
| Complementary |
|---|
| [Uimp] rated impulse withstand voltage | 8 kV |
| overvoltage category | III |
| [Ith] conventional free air thermal current | 1000 A (at 40 °C) |
| rated breaking capacity | 6400 A conforming to IEC 60947-4-1 |
| [Icw] rated short-time withstand current | 5500 A 40 °C - 10 s 4600 A 40 °C - 30 s 3600 A 40 °C - 1 min 2600 A 40 °C - 3 min 1700 A 40 °C - 10 min |
| associated fuse rating | 1000 A gG at ≤ 440 V 800 A aM at ≤ 440 V |
| average impedance | 0.12 mOhm - Ith 1000 A 50 Hz |
| [Ui] rated insulation voltage | 1000 V conforming to IEC 60947-4-1 1500 V conforming to VDE 0110 group C |
| power dissipation per pole | 120 W AC-1 77 W AC-3 |
| mounting support | Plate |
| standards | IEC 60947-1 JIS C8201-4-1 EN 60947-4-1 EN 60947-1 IEC 60947-4-1 |
| product certifications | ABS UL CCC CSA RMRoS CB |
| connections - terminals | Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end Power circuit: bar 2 cable(s) - busbar cross section: 60 x 5 mm Power circuit: bolted connection |
| tightening torque | Control circuit: 1.2 N.m Power circuit: 58 N.m |
| control circuit voltage limits | Operational: 0.85…1.1 Uc (at 55 °C) Drop-out: 0.3…0.5 Uc (at 55 °C) |
| inrush power in W | 1900 W (at 20 °C) |
| hold-in power consumption in W | 12 W at 20 °C |
| heat dissipation | 12 W |
| operating time | 40…50 ms opening 60…80 ms closing |
| mechanical durability | 5 Mcycles |
| maximum operating rate | 600 cyc/h 55 °C |
| compatibility code | LC1F |
| motor power range | 250…500 kW at 200…240 V 3 phases 250…500 kW at 380…440 V 3 phases 110…220 kW at 200…240 V 3 phases 250…500 kW at 480…500 V 3 phases |
| motor starter type | Direct on-line contactor |
| contactor coil voltage | 220 V DC standard 230 V DC standard 220 V AC standard 230 V AC standard 240 V AC standard |
| Environment |
|---|
| IP degree of protection | IP20 front face with shrouds conforming to IEC 60529 IP20 front face with shrouds conforming to VDE 0106 |
| protective treatment | TH |
| ambient air temperature for operation | -5…55 °C |
| ambient air temperature for storage | -60…80 °C |
| permissible ambient air temperature around the device | -5…55 °C |
| height | 304 mm |
| width | 309 mm |
| depth | 255 mm |
| net weight | 18.75 kg |