Monitoring relay 71.31.8.400.1021

Model: 005.066.114
Monitoring relay 71.31.8.400.1021
Manufacturer: Finder (Italy)
Monitoring relay 71.31.8.400.1021 detects over and under voltage limits in three phase 400VAC circuits.
• Adjustable under voltage trip level (0,8...0,95)Un and fixed over voltage trip level 1,15Un.
• Rated current 10A.
• Adjustable trip delay time (0,1...12)s.
• 1 change-over contact (SPDT).
• Fault memory, switch selectable.
Price by call

Technical data

Contact specification
Contact configuration1 change-over contact (SPDT)
Rated current/Peak current10A/15A
Rated voltage/Max switching voltage250VAC/400VAC
Rated load2500 VA (AC-1)
500 VA (AC-15 230VAC)
Single phase motor rating (230VAC)0.5 kW
Standard contact materialAgCdO
Supply specification
Nominal voltage (Un)400VAC
Rated power4 VA (50 Hz)
Operating range(0,8...1,15)Un
Complementary characteristics
Electrical life at rated load AC1100×103 cycles
Detection level Umin/Umax(0.8...0.95)Un/1.15Un
Trip on-delay/reaction time(0.1...12)s / <0,5s
Fault memory - selectableyes
Ambient temperature range-20°C...+55°C
Protection categoryIP 20

Dimensions and wiring diagram

Dimensions of monitoring relay 71.31.8.400.1021

Auxiliaries and accessories for 713184001021PAS

Similar or replacement products 713184001021PAS