Circuit breaker NG125L 18810 4P 10A C

Model: 003.014.100
Circuit breaker NG125L 18810
Manufacturer: Schneider Electric
Barcode: 3303430188100
The NG125L 18810 circuit breaker meets the requirements of IEC 60947-2, EN 60947-2 and combines the following functions:
  • protection of circuits against short-circuit currents
  • overload current protection
  • possibility of partitioning in industrial electrical installations in accordance with IEC / EN 60947-2
  • trip indication by means of a red mechanical status indicator located on the front of the circuit breaker
Price by call

Main

range of productNG125
rangeActi 9
product nameActi 9 NG125
product or component typeMiniature circuit-breaker
device short nameNG125L
device applicationDistribution
poles description4P
number of protected poles4
neutral positionLeft
[In] rated current10 A at 40 °C
network typeAC
DC
trip unit technologyThermal-magnetic
curve codeC
breaking capacity100 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2
40 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
50 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2
15 kA Icu at 500 V AC 50/60 Hz conforming to EN/IEC 60947-2
36 kA Icu at ≤ 500 V DC conforming to EN/IEC 60947-2
utilisation categoryCategory A conforming to IEC 60947-2
suitability for isolationYes conforming to IEC 60947-2

Complementary

network frequency50/60 Hz
[Ue] rated operational voltage380...415 V AC 50/60 Hz
500 V AC 50/60 Hz
≤ 500 V DC
220...240 V AC 50/60 Hz
440 V AC 50/60 Hz
magnetic tripping limit8 x In +/- 20 %
[Ics] rated service breaking capacity75 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz
37.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz
30 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz
11.25 kA 75 % conforming to EN/IEC 60947-2 - 500 V AC 50/60 Hz
50 kA 100 % conforming to EN/IEC 60947-2 - 500 V DC
[Ui] rated insulation voltage690 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage8 kV conforming to EN/IEC 60947-2
contact position indicatorYes
control typeManual tripping test
Toggle
local signallingTrip indicator
ON/OFF indication
mounting modeClip-on
mounting support35 mm symmetrical DIN rail
comb busbar and distribution block compatibilityYES
9 mm pitches12
height103 mm
width108 mm
depth81 mm
net weight0.96 kg
mechanical durability20000 cycles
electrical durability10000 cycles
provision for padlockingPadlockable
locking options descriptionIntegrated padlocking
connections - terminalsTunnel type terminals1.5…50 mm² rigid
Tunnel type terminals1…35 mm² flexible
wire stripping length20 mm
tightening torque3.5 N.m
earth-leakage protectionSeparate block

Environment

standardsEN/IEC 60947-2
IP degree of protectionIP20 conforming to IEC 60529
IK degree of protectionIK05 conforming to EN/IEC 62262
pollution degree3 conforming to IEC 60947-2
overvoltage categoryIV
tropicalisation2 conforming to IEC 60068-1
relative humidity95 % at 55 °C
operating altitude2000 m
ambient air temperature for operation-30…70 °C
ambient air temperature for storage-40…70 °C

Dimension

Dimension breaker NG125L 4P

Model range of cicruit breakers NG125L

Poles 1 2 3 4
Rated current, A Characteristic Trip Curves
B C D B C D B C D B C D
10 18741 18777 18830 18750 18788 18839 18759 18799 18848 18768 18810 18857
16 18742 18778 18831 18751 18789 18840 18760 18800 18849 18769 18811 18858
20 18743 18779 18832 18752 18790 18841 18761 18801 18850 18770 18812 18859
25 18744 18780 18833 18753 18791 18842 18762 18802 18851 18771 18813 18860
32 18745 18781 18834 18754 18792 18843 18763 18803 18852 18772 18814 18861
40 18746 18782 18835 18755 18793 18844 18764 18804 18853 18773 18815 18862
50 18747 18783 18836 18756 18794 18845 18765 18805 18854 18774 18816 18863
63 18748 18784 18837 18757 18795 18846 18766 18806 18855 18775 18817 18864
80 18749 18785 18838 18758 18796 18847 18767 18807 18856 18776 18818 18865

Dimensions circuit breaker NG125L

Dimensions circuit breaker NG125L

Trip curves

Tripping time according to IEC/EN60947-2 (at an ambient temperature of 50°C)
Trip curves NG125L

Auxiliaries and accessories for 18810

Similar or replacement products 18810