Circuit breaker C120H A9N18403 1P 100A B

Model: 003.001.075
Circuit breaker C120H A9N18403
Manufacturer: Schneider Electric
Barcode: 3606480379741
The C120H A9N18403 circuit breaker meets the requirements of the standards EN 60947-2, EN 60898-1 and combines the following functions:
  • protection of circuits against short-circuit currents
  • overload current protection
  • fault signaling and emergency shutdown by means of optional accessories
Price by call

Main

range of productC120
rangeActi 9
product nameC120
product or component typeMiniature circuit-breaker
device short nameC120H
device applicationDistribution
poles description1P
number of protected poles1
[In] rated current100 A at 30 °C
network typeAC
trip unit technologyThermal-magnetic
curve codeB
breaking capacity30 kA Icu at 130 V AC 50/60 Hz conforming to EN/IEC 60947-2
20 kA Icu at 12 V DC conforming to EN/IEC 60947-2
20 kA Icu at 125 V DC conforming to EN/IEC 60947-2
15 kA Icu at ≤ 144 V DC conforming to EN/IEC 60947-2
15 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2
15000 A Icn at 230...400 V AC 50/60 Hz conforming to EN/IEC 60898-1
4.5 kA Icu at 380...415 V AC 50/60 Hz IT conforming to EN/IEC 60947-2
30 kA Icu at 12 V AC 50/60 Hz conforming to EN/IEC 60947-2
suitability for isolationYes conforming to IEC 60947-2

Complementary

network frequency50/60 Hz
[Ue] rated operational voltage380...415 V AC 50/60 Hz
125 V DC
≤ 144 V DC
12 V DC
220...240 V AC 50/60 Hz
230...400 V AC 50/60 Hz
130 V AC 50/60 Hz
12 V AC 50/60 Hz
magnetic tripping limit3...5 x In
[Ics] rated service breaking capacity15 kA 50 % conforming to EN/IEC 60947-2 - 130 V AC 50/60 Hz
7.5 kA 50 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz
2.25 kA 50 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz
7500 A 50 % conforming to EN/IEC 60898-1 - 230...400 V AC 50/60 Hz
20 kA 100 % conforming to EN/IEC 60947-2 - 12 V DC
15 kA 100 % conforming to EN/IEC 60947-2 - ≤ 144 V DC
20 kA 100 % conforming to EN/IEC 60947-2 - 125 V DC
15 kA 50 % conforming to EN/IEC 60947-2 - 12 V AC 50/60 Hz
limitation class3 conforming to EN/IEC 60947-2
[Ui] rated insulation voltage500 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage6 kV conforming to EN/IEC 60947-2
contact position indicatorYes
control typeToggle
local signallingON/OFF indication
mounting modeClip-on
mounting support35 mm symmetrical DIN rail
comb busbar and distribution block compatibilityNO
9 mm pitches3
height81 mm
width27 mm
depth73 mm
net weight0.205 kg
colourWhite
mechanical durability20000 cycles
electrical durability5000 cycles conforming to IEC 60947-2
connections - terminalsTunnel type terminals1…50 mm² rigid
Tunnel type terminals1.5…35 mm² flexible
wire stripping length15 mm
tightening torque3.5 N.m
earth-leakage protectionWithout

Environment

standardsEN/IEC 60898-1
EN/IEC 60947-2
product certificationsEAC
IP degree of protectionIP20 conforming to IEC 60529
pollution degree3 conforming to IEC 60947-2
overvoltage categoryIV
tropicalisation2 conforming to IEC 60068-1
relative humidity95 % at 55 °C
operating altitude2000 m
ambient air temperature for operation-30…60 °C
ambient air temperature for storage-40…70 °C

Nomenclature of circuit breakers C120H

Dimensions circuit breaker C120H

Dimensions circuit breaker C120H

Trip curves

Curve В Curve C Curve D

Auxiliaries and accessories for A9N18403

Similar or replacement products A9N18403